Article: AF09Z-22-00-20

We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
| Extended Product Type: | AF09Z-22-00-20 |
| Product ID: | 1SBL136501R2000 |
| EAN: | 3471523116603 |
| Catalog Description: | AF09Z-22-00-20 12-20VDC Contactor |
| Long Description: | The AF09Z-22-00-20 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (12-20 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. |
| |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85364900 |
| Popular Downloads | |
| Instructions and Manuals: | 1SBC101027M6801 |
| |
| Product Net Width: | 45 mm |
| Product Net Depth / Length: | 77 mm |
| Product Net Height: | 86 mm |
| Product Net Weight: | 0.31 kg |
| |
| Number of Main Contacts NO: | 2 |
| Number of Main Contacts NC: | 2 |
| Number of Auxiliary Contacts NO: | 0 |
| Number of Auxiliary Contacts NC: | 0 |
| Standards: | IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14 |
| Rated Operational Voltage: | Main Circuit 690 V |
| Rated Frequency (f): | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith): | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A |
| Rated Operational Current AC-1 (Ie): | (690 V) 40 °C 25 |
| (690 V) 60 °C 25 A | |
| (690 V) 70 °C 22 | |
| Rated Operational Current AC-3 (Ie): | (415 V) 60 °C 9 A |
| (440 V) 60 °C 9 A | |
| (500 V) 60 °C 9.5 A | |
| (690 V) 60 °C 7 A | |
| (380 / 400 V) 60 °C 9 A | |
| (220 / 230 / 240 V) 60 °C 9 A | |
| Rated Operational Power AC-3 (Pe): | (400 V) 4 kW |
| (415 V) 4 kW | |
| (440 V) 4 kW | |
| (500 V) 5.5 kW | |
| (690 V) 5.5 kW | |
| (380 / 400 V) 4 kW | |
| (220 / 230 / 240 V) 2.2 kW | |
| Rated Short-time Withstand Current (Icw): | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| for 1 s -empty- A | |
| Maximum Breaking Capacity: | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Maximum Electrical Switching Frequency: | (AC-1) 600 cycles per hour |
| Rated Insulation Voltage (Ui): | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp): | 6 kV |
| Maximum Mechanical Switching Frequency: | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc): | 50 Hz - |
| 50 Hz / 60 Hz 100 ... 250 V | |
| 60 Hz - | |
| DC Operation 12 ... 20 V | |
| Operate Time: | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Connecting Capacity Main Circuit: | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 6 mm² | |
| Connecting Capacity Control Circuit: | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length: | Control Circuit 10 mm |
| Main Circuit 10 mm | |
| Degree of Protection: | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Terminal Type: | Screw Terminals |
| Technical UL/CSA | |
| General Use Rating UL/CSA: | (600 V AC) 25 A |
| Tightening Torque UL/CSA: | Control Circuit 11 IA |
| Main Circuit 13 IA | |
| |
| Ambient Air Temperature: | Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... +70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Near Contactor for Operation in Free Air -40 ... +70 °C | |
| Climatic Withstand: | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible: | 3000 m |
| Resistance to Vibrations acc. to IEC 60068-2-6: | 5 ... 300 Hz 4 g closed position / 2 g open position |
| Resistance to Shock acc. to IEC 60068-2-27: | Closed, Shock Direction: B1 25 K40 |
| Open, Shock Direction: B1 5 K40 | |
| Shock Direction: A 30 K40 | |
| Shock Direction: B2 15 K40 | |
| Shock Direction: C1 25 K40 | |
| Shock Direction: C2 25 K40 | |
| RoHS Status: | Following EU Directive 2011/65/EU |
| |
| ABS Certificate: | ABS_15-GE1349500-PDA_90682247 |
| BV Certificate: | BV_2634H24898B0 |
| CB Certificate: | CB_SE-96551M1 |
| CCC Certificate: | CCC_2010010304445624 |
| CQC Certificate: | CQC2010010304445624 |
| CQC2020010304298240 | |
| Declaration of Conformity - CCC: | 2020980304001253 |
| 2020980304001082 | |
| Declaration of Conformity - CE: | 1SBD250001U1000 |
| DNV Certificate: | DNV-GL_TAE00001AF-3 |
| DNV GL Certificate: | DNV-GL_TAE00001AF-3 |
| EAC Certificate: | EAC_RU_FRME77B03447 |
| Environmental Information: | 1SBD250147E1000 |
| GL Certificate: | DNV-GL_TAE00001AF-3 |
| GOST Certificate: | GOST_POCCFR.ME77.B07175.pdf |
| Instructions and Manuals: | 1SBC101027M6801 |
| KC Certificate: | KC_HW02016-15007C |
| LR Certificate: | LRS_1300087E1 |
| RINA Certificate: | RINA_ELE084013XG |
| RMRS Certificate: | RMRS_1802705280 |
| RoHS Information: | 1SBD250001U1000 |
| UL Certificate: | UL_20171228-E319322_3_1 |
| UL Listing Card: | UL_E319322 |
| |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 87 mm |
| Package Level 1 Depth / Length: | 79 mm |
| Package Level 1 Height: | 47 mm |
| Package Level 1 Gross Weight: | 0.31 kg |
| Package Level 1 EAN: | 3471523116603 |
| Package Level 2 Units: | box 27 piece |
| Package Level 2 Width: | 250 mm |
| Package Level 2 Depth / Length: | 300 mm |
| Package Level 2 Height: | 315 mm |
| Package Level 2 Gross Weight: | 16.74 kg |
| Package Level 3 Units: | 1296 piece |
| |
| Object Classification Code: | Q |
| ETIM 4: | EC000066 - Magnet contactor, AC-switching |
| ETIM 5: | EC000066 - Magnet contactor, AC-switching |
| ETIM 6: | EC000066 - Power contactor, AC switching |
| ETIM 7: | EC000066 - Power contactor, AC switching |
| eClass: | V11.0 : 27371003 |
| UNSPSC: | 39121529 |
| E-Number (Finland): | 3706346 |