Article: E3N2500PR122/P-LSIGIn=2500A4pWMP

Article: E3N2500PR122/P-LSIGIn=2500A4pWMP

E3N 2500 PR122/P-LSIG In=2500A 4p W MP
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration






















General Information
Extended Product Type: E3N2500PR122/P-LSIGIn=2500A4pWMP
Product ID: 1SDA056141R1
EAN: 8015644574819
Catalog Description: E3N 2500 PR122/P-LSIG In=2500A 4p W MP
Long Description: SACE EMAX MOVING PART FOR CIRCUIT-BREAKER E3N 2500A FOUR-POLE OVERCURRENT RELEASE PR122/P-LSIG R2500 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Ordering
EAN: 8015644574819
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090

Dimensions
Product Net Width: 558 mm
Product Net Height: 461 mm
Product Net Depth / Length: 396.5 mm
Product Net Weight: 81 kg

Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 515 mm
Package Level 1 Height: 600 mm
Package Level 1 Depth / Length: 785 mm
Package Level 1 Gross Weight: 96 kg
Package Level 1 EAN: 8015644574819

Additional Information
Current Type: AC
Electrical Durability: Ue =< 440 V 8000 cycle
Ue = 500 ... 690 V 7000 cycle
20 cycles per hour
Mechanical Durability: 20000 cycle
60 cycles per hour
Number of Poles: 4
Power Loss: 350 W
Product Main Type: SACE Emax
Product Name: Air Circuit Breaker
Product Type: Air Circuit Breaker
Rated Current (In): 2500 A
Rated Voltage (Ur): 690 V
Rated Impulse Withstand Voltage (Uimp): 12 kV
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Current (Ie): 2500 A
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 65 kA
(230 V AC) 65 kA
(380 V AC) 65 kA
(400 V AC) 65 kA
(415 V AC) 65 kA
(440 V AC) 65 kA
(500 V AC) 65 kA
(660 V AC) 65 kA
(690 V AC) 65 kA
Rated Short-time Withstand Current (Icw): for 1 s 65 kA
for 3 s 65 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 65 kA
(230 V AC) 65 kA
(380 V AC) 65 kA
(400 V AC) 65 kA
(415 V AC) 65 kA
(440 V AC) 65 kA
(500 V AC) 65 kA
(660 V AC) 65 kA
(690 V AC) 65 kA
Rated Uninterrupted Current (Iu): 2500 A
Release: PR122/P-LSIG
Release Type: EL
Short-Circuit Performance Level: N
Standards: IEC
Sub-type: E3
Terminal Connection Type: Withdrawable Circuit-Breakers
Version: W

Certificates and Declarations (Document Number)
Data Sheet, Technical Information: 1SDC200006D0209
Declaration of Conformity - CE: 1SDL000165R0015
Environmental Information: 1SDL000145R0
Instructions and Manuals: 1SDH000460R0002
1SDH000460R0102

Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 7: EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 4. Large Equipment (Any External Dimension More Than 50 cm)