General Information | |
| Product ID: | 1YMB760341M2811 |
| ABB Type Designation: | 1YMB760341M2811 |
| EAN: | 5908270807914 |
| Catalog Description: | CMF 3.6kV 250A 292/87mm S |
| Long Description: | IEC DIN motor circuit protection current limiting back-up fuse-links for indoor/outdoor application |
| |
| Product Name: | CMF 3.6kV 250A 292/87mm S |
| Catalog Number: | 1YMB760341M2811 |
| Replaced Product ID (OLD): | 1YMB531878M0004 |
| 1YMB531028M0004 | |
| EAN: | 5908270807914 |
| Made To Order: | No |
| Minimum Order Quantity: | 1 piece |
| Selling Unit of Measure: | piece |
| Country of Origin: | Poland (PL) |
| |
| Fuse Size: | e=292 mm |
| Fuse System: | DIN |
| Product Net Length: | 360 mm |
| Tube Diameter: | 87 mm |
| Product Net Height: | 87 mm |
| Product Net Width: | 87 mm |
| Package Level 1 Height: | 92 mm |
| Package Level 1 Depth / Length: | 386 mm |
| Package Level 1 Width: | 95 mm |
| Package Level 1 Units: | 1 carton |
| |
| Standards: | IEC 60282-1 |
| Rated Voltage (Ur): | 3.6 kV |
| Input Voltage Type: | AC |
| Rated Frequency (f): | 50 Hz |
| Rated Current (In): | 250 A |
| Minimum Breaking Current: | 760 A |
| Maximum Breaking Capacity: | 63 kA |
| Fuse Pre-arcing Joule Integral: | 140000 A²·s |
| Fuse Operating Joule Integral: | 1150000 A²·s |
| Power Loss: | 90 W |
| Options Available: | With striker |
| Striker Pin Rating: | 80 N |
| TCU (Temperature Control Unit): | Yes |
| Product Net Weight: | 3.6 kg |
| |
| ETIM 7: | EC003507 - Medium-/high voltage fuse |
| ETIM 8: | EC003507 - Medium-/high voltage fuse |