Article: S802PV-M63-H

We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | S802PV-M63-H |
Product ID: | 2CCP247205R0001 |
EAN: | 7612271419042 |
Catalog Description: | S802PV-M63-H High Performance MCB |
Long Description: | The S802PV-M63-H is a 2-pole polarized disconnector for photovoltaics. It can be used for currents up to 63A and has a rated operational voltage of 1000V DC by only 54mm width. The rated short-term withstand current Icw is 1.5kA. The S802PV-M63-H complies with IEC/EN 60947-3. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802PV-M63-H more comfortable. |
| |
Standards: | IEC/EN 60947-3 |
Product Name: | High Performance MCB |
Rated Operational Voltage: | 800 V DC |
Rated Insulation Voltage (Ui): | 1500 V DC |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Current (In): | 63 A |
Rated Operational Current (Ie): | 63 A |
Rated Short-Circuit Making Capacity (Icm): | (1000 V DC) 0.5 kA |
Rated Short-time Withstand Current Low Voltage (Icw): | 1.5 kA |
Rated Uninterrupted Current (Iu): | 63 A |
Power Loss: | 1.8 W |
at Rated Operating Conditions per Pole 0.9 W | |
Contact Position Indication: | ON / OFF / TRIP |
Number of Poles: | 2 |
Number of Switches: | 8500 |
Overvoltage Category: | IV |
Tightening Torque: | 3.5 N·m |
Actuator Marking: | I / O |
Housing Material: | Insulation group I, RAL 7035 |
Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
Mounting Position: | Any |
Recommended Screw Driver: | Pozidriv 2 |
Control Element Color: | Black |
Connecting Capacity: | Flexible 1 ... 50 mm² |
Stranded 1 ... 70 mm² | |
Terminal Type: | Screw Terminals |
| |
Ambient Air Temperature: | Operation -25 ... +60 °C |
Storage -40 ... +70 °C | |
Degree of Protection: | IP20 |
Pollution Degree: | 2 |
Environmental Conditions: | Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle |
Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96% | |
Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100% | |
Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C | |
Dry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C | |
Resistance to Vibrations acc. to IEC 60068-2-6: | 2 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
Resistance to Shock acc. to IEC 60068-2-27: | 5 g |
30 ms | |
RoHS Status: | Following EU Directive 2011/65/EU |
Environmental Information: | 2CCY413207D0203 |
| |
Product Net Width: | 54 mm |
Product Net Height: | 95 mm |
Product Net Depth / Length: | 82.5 mm |
Product Net Weight: | 490 g |
Product Net Length: | 54 mm |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 105 mm |
Package Level 1 Height: | 99 mm |
Package Level 1 Depth / Length: | 60 mm |
Package Level 1 Gross Weight: | 520 g |
Package Level 1 EAN: | 7612271419042 |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362010 |
E-Number (Finland): | 3601709 |
Country of Origin: | Switzerland (CH) |
Selling Unit of Measure: | piece |
| |
Declaration of Conformity - CE: | 2CCC005117D0201 |
Environmental Information: | 2CCY413207D0203 |
Instructions and Manuals: | 9AKK107046A5390 |
RoHS Information: | 2CCC005117D0201, 9AKK107680A3903 |
Popular Downloads | |
Data Sheet, Technical Information: | 2CCC413003C0208 |
Instructions and Manuals: | 9AKK107046A5390 |
| |
ETIM 6: | EC000216 - Switch disconnector |
ETIM 7: | EC000216 - Switch disconnector |
ETIM 8: | EC000216 - Switch disconnector |
EPLAN Catalog Tree: | Electrical engineering / Protection devices / General |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B: | Business To Business |
CN8: | 85362020 |
Object Classification Code: | F |