Article: S1B 125 R 125 I 1250 3p F FC

Article: S1B 125 R 125 I 1250 3p F FC
S1B 125 R 125 I 1250 3p F FC
We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | S1B 125 R 125 I 1250 3p F FC |
Product ID: | 1SDA000024R1 |
ABB Type Designation: | S1B 125 R125 FFC 3P |
EAN: | 8015644000240 |
Catalog Description: | S1B 125 R 125 I 1250 3p F FC |
Long Description: | C.BREAKER ISOMAX S1B 125 FIXED THREE-POLE WITH . FRONT TERMINALS FOR CABLE AND . THERMOMAGNETIC RELEASE A.C. R 125-1250 A |
| |
EAN: | 8015644000240 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
| |
Product Net Width: | 130 mm |
Product Net Height: | 130 mm |
Product Net Length: | 150 mm |
Product Net Depth / Length: | 0.07 m |
Product Net Weight: | 0.95 kg |
| |
Package Level 1 Units: | 1 piece |
Package Level 1 Height: | 130 mm |
Package Level 1 Depth / Length: | 130 mm |
Package Level 1 Gross Weight: | 1.05 kg |
Package Level 1 EAN: | 8015644000240 |
| |
RoHS Status: | No declaration needed |
| |
Electrical Durability: | 8000 |
Number of Poles: | 3 |
Order Multiple: | 1.000 piece |
Power Loss: | 25 W |
Product Main Type: | SACE Isomax |
Product Name: | Moulded Case Circuit Breaker |
Rated Current (In): | 125 A |
Rated Impulse Withstand Voltage (Uimp): | 6 kV |
Rated Operational Voltage: | 500 V AC |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA |
(230 V AC) 25 kA | |
(380 V AC) 16 kA | |
(440 V AC) 10 kA | |
(500 V AC) 8 kA | |
Rated Uninterrupted Current (Iu): | 125.0 A |
Release Type: | TM10 |
Short-Circuit Performance Level: | B |
Standards: | IEC-947-2(D) |
Sub-type: | S1 |
Suitable For: | Isomax S1 |
Suitable for Product Class: | Isomax |
Terminal Connection Type: | Front for Copper Cables |
Test Voltage at Industrial Frequency for 1 Minute: | 3000 V |
Version: | Fixed |
| |
Data Sheet, Technical Information: | ITSCE-604050012 |
Declaration of Conformity - CE: | ITSCE-S1B125 |
Environmental Information: | 1sde000005-001 |
Instructions and Manuals: | ITSCE-601780004 |
RoHS Information: | 1SDL000194R0001 |
| |
ETIM 4: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 6: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
Object Classification Code: | Q |
UNSPSC: | 39120000 |