Article: T2H 160 MF12,5 Im=163A 3p F F

Article: T2H 160 MF12,5 Im=163A 3p F F
T2H 160 MF12,5 Im=163A 3p F F
We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | T2H 160 MF12,5 Im=163A 3p F F |
Product ID: | 1SDA053142R1 |
EAN: | 8015644539924 |
Catalog Description: | T2H 160 MF12,5 Im=163A 3p F F |
Long Description: | C.BREAKER TMAX T2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MF Iu 12,5 A Im163 A |
| |
EAN: | 8015644539924 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
| |
Product Net Width: | 90 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
| |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.2 kg |
Package Level 1 EAN: | 8015644539924 |
| |
Electrical Durability: | 8000 cycle |
120 cycles per hour | |
Mechanical Durability: | 25000 cycle |
240 cycles per hour | |
Number of Poles: | 3 |
Power Loss: | at Rated Operating Conditions per Pole 1,1 W |
Product Main Type: | SACE Tmax T |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | CB |
Rated Current (In): | 12.5 A |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC |
500 V DC | |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 100 kA |
(230 V AC) 100 kA | |
(380 V AC) 70 kA | |
(400 V AC) 70 kA | |
(415 V AC) 70 kA | |
(440 V AC) 55 kA | |
(500 V AC) 36 kA | |
(690 V AC) 8 kA | |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 10 kA |
(230 V AC) 10 kA | |
(380 V AC) 70 kA | |
(400 V AC) 70 kA | |
(415 V AC) 70 kA | |
(440 V AC) 55 kA | |
(500 V AC) 36 kA | |
(690 V AC) 8 kA | |
(250 V DC) 2 Poles in Series 70 kA | |
(250 V DC) 3 Poles in Series 85 kA | |
(500 V DC) 3 Poles in Series 70 kA | |
Rated Uninterrupted Current (Iu): | 160 A |
Release: | MF |
Release Type: | M |
Short-Circuit Performance Level: | H |
Standards: | IEC 60947 |
Sub-type: | T2 |
Suitable For: | T2 |
Suitable for Product Class: | Moulded Case Circuit Breakers |
Terminal Connection Type: | Fixed Circuit-Breakers |
Front | |
Test Voltage Max (Utest): | 3000 V |
Test Voltage at Industrial Frequency for 1 Minute: | 3000 V |
Version: | F |
| |
Data Sheet, Technical Information: | 1SDC210004D0203 |
Declaration of Conformity - CE: | 1SDL000165R0002 |
Environmental Information: | 1SDL000140R0 |
GL Certificate: | 1SDL000163R0059 |
Instructions and Manuals: | ITSCE-RH0012001 |
Instructions and Manuals (Part 2): | ITSCE-RH0100.001 |
RoHS Information: | 1SDL000200R0001 |
| |
Object Classification Code: | Q |
UNSPSC: | 39121100 |