Article: T2H 160 TMD6,3-63 4p F F

Article: T2H 160 TMD6,3-63 4p F F

T2H 160 TMD6,3-63 4p F F
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration






















General Information
Extended Product Type: T2H 160 TMD6,3-63 4p F F
Product ID: 1SDA051056R1
EAN: 8015644514785
Catalog Description: T2H 160 TMD6,3-63 4p F F
Long Description: C.BREAKER TMAX T2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 6,3-63 A

Ordering
EAN: 8015644514785
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090

Dimensions
Product Net Width: 120 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.45 kg

Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.55 kg
Package Level 1 EAN: 8015644514785

Additional Information
Electrical Durability: 8000 cycle
120 cycles per hour
Mechanical Durability: 25000 cycle
240 cycles per hour
Number of Poles: 4
Power Loss: at Rated Operating Conditions per Pole 3,5 W
Product Main Type: SACE Tmax T
Product Name: Moulded Case Circuit Breaker
Product Type: CB
Rated Current (In): 6.3 A
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 100 kA
(230 V AC) 100 kA
(380 V AC) 70 kA
(400 V AC) 70 kA
(415 V AC) 70 kA
(440 V AC) 55 kA
(500 V AC) 36 kA
(690 V AC) 8 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 10 kA
(230 V AC) 10 kA
(380 V AC) 70 kA
(400 V AC) 70 kA
(415 V AC) 70 kA
(440 V AC) 55 kA
(500 V AC) 36 kA
(690 V AC) 8 kA
(250 V DC) 2 Poles in Series 70 kA
(250 V DC) 3 Poles in Series 85 kA
(500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu): 160 A
Release: TMD
Release Type: TM
Short-Circuit Performance Level: H
Standards: IEC 60947
Sub-type: T2
Suitable For: T2
Suitable for Product Class: Moulded Case Circuit Breakers
Terminal Connection Type: Fixed Circuit-Breakers
Front
Test Voltage Max (Utest): 3000 V
Test Voltage at Industrial Frequency for 1 Minute: 3000 V
Version: F

Certificates and Declarations (Document Number)
Data Sheet, Technical Information: 1SDC210004D0203
Declaration of Conformity - CE: 1SDL000165R0002
Environmental Information: 1SDL000140R0
GL Certificate: 1SDL000163R0059
Instructions and Manuals: ITSCE-RH0012001
Instructions and Manuals (Part 2): ITSCE-RH0100.001
RoHS Information: 1SDL000200R0001
Data Sheet, Technical Information (Part 2): 1SDM000030R0001

Classifications
Object Classification Code: Q
UNSPSC: 39121100