Article: S803S-UCB3

We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
| Extended Product Type: | S803S-UCB3 |
| Product ID: | 2CCF030057R0001 |
| EAN: | 7612271500801 |
| Catalog Description: | S803S-UCB3 High Performance MCB |
| Long Description: | S803S-UCB3 3 Poles UC-B Characteristic 3A 50 kA 750 VDC High Performance Circuit Breaker HPCB |
| |
| Standards: | IEC/EN 60947-2 |
| Product Name: | High Performance MCB |
| Tripping Characteristic: | UC-B |
| Rated Operational Voltage: | 750 V DC |
| acc. to IEC 60898-1 750 V | |
| Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 1000 V |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Input Voltage Type: | DC |
| Rated Current (In): | 3 A |
| Rated Operational Current (Ie): | 3 A |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (750 V DC) 50 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (750 V DC) 50 kA |
| Rated Frequency (f): | 50...60 Hz |
| Power Loss: | 7.2 W |
| at Rated Operating Conditions per Pole 2.4 W | |
| Contact Position Indication: | ON / OFF / TRIP |
| Energy Limiting Class: | 3 |
| Number of Poles: | 3 |
| Number of Protected Poles: | 3 |
| Overvoltage Category: | III |
| Tightening Torque: | 3.5 N·m |
| Actuator Marking: | I / O |
| Housing Material: | Insulation group I, RAL 7035 |
| Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position: | Any |
| Recommended Screw Driver: | Pozidriv 2 |
| Accessories Available: | Yes |
| Remarks: | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw |
| Connecting Capacity: | Rigid 1 ... 50 mm² |
| Flexible 1 ... 70 mm² | |
| Terminal Type: | Screw Terminals |
| |
| Ambient Air Temperature: | Operation -25 ... +60 °C |
| Storage -40 ... +70 °C | |
| Degree of Protection: | acc. to IEC 60529 IP20 |
| Pollution Degree: | 2 |
| Environmental Conditions: | Damp Heat Cyclic acc. to IEC 60068-2-30 197 + 12 cycle |
| Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96 % | |
| Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100 % | |
| Dry Heat Test B acc. to IEC 60068-2-2 16 hours @ 55 °C | |
| Dry Heat Test B acc. to IEC 60068-2-2 2 hours @ 70 °C | |
| Resistance to Vibrations acc. to IEC 60068-2-6: | 7 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
| RoHS Status: | Following EU Directive 2011/65/EU |
| Environmental Information: | 2CCY413207D0203 |
| |
| Width in Number of Modular Spacings: | 4.5 |
| Product Net Width: | 81 mm |
| Product Net Height: | 95 mm |
| Product Net Depth / Length: | 82.5 mm |
| Product Net Weight: | 735 g |
| Built-In Depth (t2): | 82.5 mm |
| |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 105 mm |
| Package Level 1 Height: | 99 mm |
| Package Level 1 Depth / Length: | 60 mm |
| Package Level 1 Gross Weight: | 775 g |
| Package Level 1 EAN: | 7612271500801 |
| |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362010 |
| Country of Origin: | Switzerland (CH) |
| Selling Unit of Measure: | piece |
| |
| Declaration of Conformity - CE: | 2CCC005084D0202 |
| Environmental Information: | 2CCY413207D0203 |
| Instructions and Manuals: | 2CCC413016M0008 |
| RoHS Information: | 2CCC005084D0202, 9AKK107680A3903 |
| Popular Downloads | |
| Data Sheet, Technical Information: | 2CCC413003C0208 |
| Instructions and Manuals: | 2CCC413016M0008 |
| |
| ETIM 6: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 7: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 8: | EC000042 - Miniature circuit breaker (MCB) |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Business |
| CN8: | 85362020 |
| Object Classification Code: | F |