Article: TNL31ERT 90-150V DC

Article: TNL31ERT 90-150V DC

TNL31ERT 90-150V DC Contactor Relay
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration


























General Information
Extended Product Type: TNL31ERT 90-150V DC
Product ID: 1SBH143060R6631
EAN: 3471522364074
Catalog Description: TNL31ERT 90-150V DC Contactor Relay
Long Description: TNL... contactor relays are used for switching auxiliary circuits and control circuits - Poles: 4-pole contactor relays (mechanically linked contact elements available) - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available TNL... contactor relays are fitted with low consumption DC coils and offer a large coil voltage range.

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SNC001003C0202
Instructions and Manuals: 1SBC101006M5501
Dimension Diagram: FPTE307902

Dimensions
Product Net Width: 44 mm
Product Net Depth / Length: 97 mm
Product Net Height: 78 mm
Product Net Weight: 0.52 kg

Technical
Number of Main Contacts NO: 0
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 3
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Supply Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Short-Circuit Protective Devices: Auxiliary Circuit - gG Type Fuses 10 A
Maximum Electrical Switching Frequency: 1200 cycles per hour
Rated Operational Current DC-13 (Ie): (24 V) 6 / 144 A
(48 V) 2.8 / 134 A
(72 V) 1 / 72 A
(125 V) 0.55 / 69 A
(250 V) 0.3 / 75 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 6 kV
Mechanical Durability: > 20 million
Maximum Mechanical Switching Frequency: 6000 cycles per hour
Rated Control Circuit Voltage (Uc): DC Operation 90 ... 150 V
Coil Consumption: Holding DC (Umin / Umax) 2.5 / 8.5 W
Pull-in DC (Umin / Umax) 2.5 / 8.5 W
Operate Time: Between Coil De-energization and NC Contact Closing 16 ... 27 ms
Between Coil De-energization and NO Contact Opening 10 ... 17 ms
Between Coil Energization and NC Contact Opening 20 ... 70 ms
Between Coil Energization and NO Contact Closing 50 ... 100 ms
Connecting Capacity Auxiliary Circuit: Rigid or Flexible with Cable Lug 0.75 ... 2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10
Terminal Type: Ring-Tongue Terminals

Environmental
Ambient Air Temperature: Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air -40 ... 55 °C
Climatic Withstand: acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 10 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B2 10 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 14 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 10 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 8 m/s²
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 8 m/s²
RoHS Status: Following EU Directive 2011/65/EU

Certificates and Declarations (Document Number)
CB Certificate: CB_SE_66912A1
CCC Certificate: CCC_2012010304558126
CCC_2006010304170816
CQC Certificate: CQC2012010304558126
CSA Certificate: CSA_1041746
cUR Certificate: UL_20140915-E252354_4_2
Declaration of Conformity - CCC: 2020980303000256
Declaration of Conformity - CE: 1SBD250808U1000
EAC Certificate: EAC_RU C-FR ME77 B01006
Environmental Information: 1SBD250127E1002
GOST Certificate: GOST_POCCFRME77B07174
Instructions and Manuals: 1SBC101006M5501
RoHS Information: 1SBD250808U1000
UL Certificate: UL_20140915-E252354_4_2
UL Listing Card: UL_E252354

Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 86 mm
Package Level 1 Depth / Length: 141 mm
Package Level 1 Height: 51 mm
Package Level 1 Gross Weight: 0.52 kg
Package Level 1 EAN: 3471522364074

Classifications
Object Classification Code: K
ETIM 4: EC000196 - Contactor relay
ETIM 5: EC000196 - Contactor relay
ETIM 6: EC000196 - Contactor relay
ETIM 7: EC000196 - Contactor relay
eClass: V11.0 : 27371018
UNSPSC: 39121500