Article: T4N 250 UL/CSA PR221DS-LS/I 250 3p F F

Article: T4N 250 UL/CSA PR221DS-LS/I 250 3p F F

T4N 250 UL/CSA PR221DS-LS/I 250 3p F F
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration












General Information
Extended Product Type: T4N 250 UL/CSA PR221DS-LS/I 250 3p F F
Product ID: 1SDA055413R1
EAN: 8015644567149
Catalog Description: T4N 250 UL/CSA PR221DS-LS/I 250 3p F F
Long Description: C.BREAKER TMAX T4N 250 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-LS/I R 250

Ordering
EAN: 8015644567149
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090

Dimensions
Product Net Weight: 1 kg

Container Information
Package Level 1 EAN: 8015644567149

Additional Information
Mechanical Durability: 20000 cycle
Number of Poles: 3
Power Loss: at Rated Operating Conditions per Pole 10.7 W
Product Main Type: SACE Tmax T
Product Name: Moulded Case Circuit Breaker
Product Type: CB
Rated Current (In): 250 A
Rated Operational Voltage: 600 V AC
600 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (240 V AC) 65 A
(480 V AC) 25 A
(600 V AC) 18 A
(500 V DC) 25 A
(600 V DC) 16 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (240 V AC) 65 kA
(480 V AC) 25 kA
(600 V AC) 18 kA
(500 V DC) 2 Poles in Series 25 kA
(600 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu): 250 A
Release: PR221DS-LS/I
Release Type: EL
Short-Circuit Performance Level: N
Standards: UL 489
CSA C22.2
Sub-type: T4
Terminal Connection Type: Fixed Circuit-Breakers
Front
Test Voltage Max (Utest): 3500 V
Version: F

Certificates and Declarations (Document Number)
Data Sheet, Technical Information: 9AKK105713A5947
Declaration of Conformity - CE: 1SDL000165R0004
Instructions and Manuals: 1SDC210023D0201

Classifications
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)