Article: BC6-22-00-P-04

Article: BC6-22-00-P-04
BC6-22-00-P-04 Mini Contactor 110-125VDC
We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | BC6-22-00-P-04 |
Product ID: | GJL1213509R0004 |
EAN: | 4013614157592 |
Catalog Description: | BC6-22-00-P-04 Mini Contactor 110-125VDC |
Long Description: | The BC6-22-00-P mini contactor is a compact 4 pole contactor with soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 4 kW (AC-3) and 20 A / 690 V (AC-1) or switching of control signals. Further features are the noiseless and hum-free coil and a switch position indication. |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85365080 |
Popular Downloads | |
Data Sheet, Technical Information: | 1SBC100214C0202 |
Instructions and Manuals: | 2CDC102047M6801 |
Dimension Diagram: | GJL1200438F0001 |
| |
Product Net Width: | 47.5 mm |
Product Net Height: | 45.5 mm |
Product Net Depth / Length: | 51.5 mm |
Product Net Weight: | 0.17 kg |
| |
Number of Poles: | 4 |
Mini Contactor Type: | Mini Contactor |
Rated Operational Voltage: | Main Circuit 690 V AC |
Main Circuit 220 V DC | |
Rated Frequency (f): | Control Circuit DC |
Main Circuit 60 Hz | |
Main Circuit 50 Hz | |
Main Circuit DC | |
Rated Impulse Withstand Voltage (Uimp): | Main Circuit 6 kV |
Rated Insulation Voltage (Ui): | 690 V |
acc. to UL/CSA 600 V | |
Number of Main Contacts NC: | 2 |
Number of Main Contacts NO: | 2 |
Rated Operational Current AC-1 (Ie): | (220 / 240 V) 40 °C 12 A |
(220 / 240 V) 55 °C 12 A | |
(380 / 440 V) 40 °C 12 A | |
(380 / 440 V) 55 °C 12 A | |
(690 V) 40 °C 6 A | |
(690 V) 55 °C 6 A | |
Rated Operational Power AC-3 (Pe): | (230 V) Three Phase 2.2 kW |
(400 V) Three Phase 4 kW | |
(500 V) Three Phase 4 kW | |
(690 V) Three Phase, NC 3 kW | |
(690 V) Three Phase, NO 3 kW | |
Rated Short-time Withstand Current (Icw): | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A |
Number of Auxiliary Contacts NC: | 0 |
Number of Auxiliary Contacts NO: | 0 |
Conventional Free-air Thermal Current (Ith): | Main Circuit 12 A |
Rated Control Circuit Voltage (Uc): | 110 ... 125 V DC |
Coil Operating Limits: | (acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
Degree of Protection: | Auxiliary Circuit Terminals IP20 |
Control Circuit Terminals IP20 | |
Main Circuit Terminals IP20 | |
Mechanical Durability: | 10000000 cycle |
Maximum Electrical Switching Frequency: | (AC-1) 300 cycles per hour |
(AC-15) 360 cycles per hour | |
(AC-3) 600 cycles per hour | |
(DC-1) 600 cycles per hour | |
(DC-13) 360 cycles per hour | |
(DC-3) 600 cycles per hour | |
Mounting on DIN Rail: | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | |
Standards: | IEC/EN 60947-1 |
IEC/EN 60947-4-1 | |
IEC/EN 60947-5-1 | |
UL 60947-1 | |
UL 60947-4-1 | |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA: | Main Circuit 600 V AC |
Full Load Amps Motor Use: | (115 V AC) Single Phase 5.8 A |
(200 V AC) Three Phase 4.8 A | |
(220 ... 240 V AC) Three Phase 6.8 A | |
(230 V AC) Single Phase 4.9 A | |
(440 ... 480 V AC) Three Phase 4.8 A | |
(550 ... 600 V AC) Three Phase 1.7 A | |
Horsepower Rating UL/CSA: | (115 V AC) Single Phase 0.25 Hp |
(200 V AC) Three Phase 1 Hp | |
(220 ... 240 V AC) Three Phase 2 Hp | |
(230 V AC) Single Phase 0.5 Hp | |
(440 ... 480 V AC) Three Phase 3 Hp | |
(550 ... 600 V AC) Three Phase 1 Hp | |
General Use Rating UL/CSA: | (300 V AC) 8 A |
| |
Ambient Air Temperature: | Operation -20 ... +55 °C |
Storage -40 ... +80 °C | |
Maximum Operating Altitude Permissible: | 2000 m |
Resistance to Shock acc. to IEC 60068-2-27: | 11 ms Pulse 15g |
Resistance to Vibrations acc. to IEC 60068-2-6: | 5g / 5 ... 150 Hz |
RoHS Status: | Following EU Directive 2011/65/EU |
| |
BV Certificate: | 1SAA920000-0204 |
CB Certificate: | 1SAA938000-2002 |
CQC Certificate: | CQC2003010304064033 |
cURus Certificate: | cUL_E191658 |
Declaration of Conformity - CCC: | 2020980304001854 |
Declaration of Conformity - CE: | 1SAD938517-0001 |
Declaration of Conformity - UKCA: | 1SAD938500-1001 |
DNV GL Certificate: | 1SAA938000-0306 |
EAC Certificate: | 1SAA920000-2702 |
Environmental Information: | 1SAC200067H0009 |
Instructions and Manuals: | 2CDC102047M6801 |
KC Certificate: | 1SAA938000-1501 |
LR Certificate: | 1SAA938000-0504 |
RMRS Certificate: | 1SAA938000-0704 |
RoHS Information: | 1SAD938517-0001 |
| |
Package Level 1 Units: | 10 piece |
Package Level 1 Width: | 108 mm |
Package Level 1 Height: | 69 mm |
Package Level 1 Depth / Length: | 247 mm |
Package Level 1 Gross Weight: | 1.775 kg |
Package Level 1 EAN: | 4013614415692 |
| |
Object Classification Code: | Q |
ETIM 4: | EC000066 - Magnet contactor, AC-switching |
ETIM 5: | EC000066 - Magnet contactor, AC-switching |
ETIM 6: | EC000066 - Power contactor, AC switching |
ETIM 7: | EC000066 - Power contactor, AC switching |
eClass: | V11.0 : 27371003 |
UNSPSC: | 39121529 |
Accessories |