Article: S802S-UCK0.5

We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | S802S-UCK0.5 |
Product ID: | 2CCF019999R0001 |
EAN: | 7612271500658 |
Catalog Description: | S802S-UCK0.5 High Performance MCB |
Long Description: | S802S-UCK0.5 2 Poles UC-K Characteristic 0.5A 50 kA 500 VDC High Performance Circuit Breaker HPCB |
| |
Standards: | IEC/EN 60947-2 |
Product Name: | High Performance MCB |
Tripping Characteristic: | UC-K |
Rated Operational Voltage: | 500 V DC |
acc. to IEC 60898-1 500 V | |
Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 1000 V |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Input Voltage Type: | DC |
Rated Current (In): | 0.5 A |
Rated Operational Current (Ie): | 0.5 A |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (500 V DC) 50 kA |
Rated Service Short-Circuit Breaking Capacity (Ics): | (500 V DC) 50 kA |
Rated Frequency (f): | 50...60 Hz |
Power Loss: | 4 W |
at Rated Operating Conditions per Pole 2 W | |
Contact Position Indication: | ON / OFF / TRIP |
Energy Limiting Class: | 3 |
Number of Poles: | 2 |
Number of Protected Poles: | 2 |
Overvoltage Category: | III |
Tightening Torque: | 3.5 N·m |
Actuator Marking: | I / O |
Housing Material: | Insulation group I, RAL 7035 |
Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
Mounting Position: | Any |
Recommended Screw Driver: | Pozidriv 2 |
Accessories Available: | Yes |
Remarks: | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw |
Connecting Capacity: | Rigid 1 ... 50 mm² |
Flexible 1 ... 70 mm² | |
Terminal Type: | Screw Terminals |
| |
Ambient Air Temperature: | Operation -25 ... +60 °C |
Storage -40 ... +70 °C | |
Degree of Protection: | acc. to IEC 60529 IP20 |
Pollution Degree: | 2 |
Environmental Conditions: | Damp Heat Cyclic acc. to IEC 60068-2-30 185 + 12 cycle |
Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96 % | |
Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100 % | |
Dry Heat Test B acc. to IEC 60068-2-2 16 hours @ 55 °C | |
Dry Heat Test B acc. to IEC 60068-2-2 2 hours @ 70 °C | |
Resistance to Vibrations acc. to IEC 60068-2-6: | 7 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
RoHS Status: | Following EU Directive 2011/65/EU |
Environmental Information: | 2CCY413207D0203 |
| |
Width in Number of Modular Spacings: | 3 |
Product Net Width: | 54 mm |
Product Net Height: | 95 mm |
Product Net Depth / Length: | 82.5 mm |
Product Net Weight: | 0.49 kg |
Built-In Depth (t2): | 82.5 mm |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 105 mm |
Package Level 1 Height: | 99 mm |
Package Level 1 Depth / Length: | 60 mm |
Package Level 1 Gross Weight: | 510 g |
Package Level 1 EAN: | 7612271500658 |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362010 |
Country of Origin: | Switzerland (CH) |
Selling Unit of Measure: | piece |
| |
Declaration of Conformity - CE: | 2CCC005084D0202 |
Environmental Information: | 2CCY413207D0203 |
Instructions and Manuals: | 2CCC413016M0008 |
RoHS Information: | 2CCC005084D0202, 9AKK107680A3903 |
Popular Downloads | |
Data Sheet, Technical Information: | 2CCC413003C0208 |
Instructions and Manuals: | 2CCC413016M0008 |
| |
ETIM 6: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 7: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 8: | EC000042 - Miniature circuit breaker (MCB) |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B: | Business To Business |
CN8: | 85362020 |
Object Classification Code: | F |