Article: MO165-80B

Article: MO165-80B

MO165-80B Manual Motor Starter Magnetic Only
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration



















































General Information
Extended Product Type: MO165-80B
Product ID: 1SAM461200R1019
EAN: 4013614560675
Catalog Description: MO165-80B Manual Motor Starter Magnetic Only
Long Description: MO165-B is a compact and powerful range for starter protection up to 45 kW (400 V AC) / 80 A in width of 55 mm. Manual motor starters magnetic only are electromechanical protection devices for the main circuit, complying with the latest railway rolling stock standards and allowing installation in passengers or driver cabins for trains frequently operating tunnels or undergrounds. They are used mainly to switch motors manually ON/OFF and protect them fuseless against short-circuits.Fuseless protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Fuse-less starter combinations are setup together with contactors and overload relays.– designed in accordance to the applicable parts of IEC 60077 standard– shocks and vibration withstand conforming to IEC 61373 (category 1, class B)– usable according to European fire and smoke safety standard EN 45545-2

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Popular Downloads
Data Sheet, Technical Information: 1SBC100200C02__
Data Sheet, Technical Information (Part 2): 1SAM400506F0001
1SAM400507F0001
Instructions and Manuals: 2CDC131082M6801
Instructions and Manuals (Part 2): 2CDC131060M0202
Dimension Diagram: 1SAM400402F0001

Dimensions
Product Net Width: 55 mm
Product Net Height: 142.65 mm
Product Net Depth / Length: 122 mm
Product Net Weight: 1 kg

Technical
Rated Service Short-Circuit Breaking Capacity (Ics): (230 V AC) 30 kA
(250 V DC) 3 Poles in Series 100 kA
(400 V AC) 30 kA
(440 V AC) 18 kA
(500 V AC) 10 kA
(690 V AC) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (230 V AC) 30 kA
(250 V DC) 100 kA
(400 V AC) 30 kA
(440 V AC) 18 kA
(500 V AC) 10 kA
(690 V AC) 8 kA
Rated Instantaneous Short-Circuit Current Setting (Ii): 1120 A
Setting Range: None
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 45 kW
Rated Operational Power AC-3e (Pe): (400 V) Three Phase 45 kW
Rated Operational Voltage: Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie): 80 A
Rated Operational Current AC-3 (Ie): 80 A
Rated Operational Current AC-3e (Ie): 80 A
Rated Operational Current DC-5 (Ie): 80 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Rated Insulation Voltage (Ui): 1000 V
Power Loss: at Rated Operating Conditions per Pole 6.27 W
Number of Poles: 3
Conventional Free-air Thermal Current (Ith): Main Circuit 80 A
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 20000 cycle
Mechanical Durability: 50000 cycle
Terminal Type: Screw Terminals
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 1 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²
Flexible 1/2x 1 ... 35 mm²
Rigid 1/2x 1 ... 4 mm²
Solid 1/2x 1 ... 4 mm²
Stranded 1/2x 1 ... 50 mm²
Tightening Torque: Main Circuit 4 N·m
Wire Stripping Length: Main Circuit 16 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance: Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mm
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF / TRIP
Standards: IEC 60077-1 (applicable parts)
IEC 60077-2 (applicable parts)
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
Remarks: For overload protection of the motors, an appropriate thermal or electronic overload relays must be used
Technical UL/CSA
Short-Circuit Current Rating (SCCR): Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 10 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 10 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 50 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 10 kA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V AC
Ampere Rating UL/CSA: 80 A
Horsepower Rating UL/CSA: (200 V AC) Three Phase 25 Hp
(208 V AC) Three Phase 25 Hp
(220 ... 240 V AC) Three Phase 30 Hp
(440 ... 480 V AC) Three Phase 60 Hp
(550 ... 600 V AC) Three Phase 75 Hp
Full Load Amps Motor Use: (110 ... 120 V AC) Three Phase 56 A
(200 V AC) Three Phase 78.2 A
(208 V AC) Three Phase 74.8 A
(220 ... 240 V AC) Three Phase 80 A
(440 ... 480 V AC) Three Phase 77 A
(550 ... 600 V AC) Three Phase 77 A
Locked Rotor Amps: (200 V AC) Three Phase 420 A
(208 V AC) Three Phase 404 A
(220 ... 240 V AC) Three Phase 435 A
(440 ... 480 V AC) Three Phase 435 A
(550 ... 600 V AC) Three Phase 434 A
General Use Rating UL/CSA: (600 V AC) 80 A
Connecting Capacity Main Circuit UL/CSA: Flexible 1/2x 16-0 AWG
Stranded 1/2x 16-0 AWG
Tightening Torque UL/CSA: Main Circuit 35 in·lb

Environmental
Ambient Air Temperature: Operation -25 ... +60 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature Compensation: No
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-6: 5g / 3 ... 150 Hz

Certificates and Declarations (Document Number)
Declaration of Conformity - CE: 1SAD938505-0198
Environmental Information: 1SAC200051H0009
Instructions and Manuals: 2CDC131082M6801
Instructions and Manuals (Part 2): 2CDC131060M0202
RoHS Information: 1SAD938501-0198

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 78 mm
Package Level 1 Depth / Length: 155 mm
Package Level 1 Height: 155 mm
Package Level 1 Gross Weight: 1.1 kg
Package Level 1 EAN: 4013614560675
Package Level 2 Units: carton 12 piece
Package Level 2 Width: 330 mm
Package Level 2 Depth / Length: 400 mm
Package Level 2 Height: 320 mm
Package Level 2 Gross Weight: 13 kg
Package Level 2 EAN: 4013614560682

Classifications
Object Classification Code: F
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
ETIM 7: EC000074 - Motor protection circuit-breaker
eClass: V11.0 : 27370401
UNSPSC: 39121521
IDEA Granular Category Code (IGCC): 4845 >> 3 Pole Motor Circuit Protector Circuit Breakers