Article: OKA20S3RF2

We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | OKA20S3RF2 |
Product ID: | 1SCA150645R1001 |
EAN: | 6417019807607 |
Catalog Description: | OKA20S3RF2 F200 EMC Enclosed Switch |
Long Description: | The ABB fire rated switches withstand fire acc. to standard EN12101-3. ABB can prodvide products for class F200 (120min), F300 (120min) and F400 (120min). Typical applications are high rise buildings, car parks, tunnels or any other place where there are exhaust fans that should stay on during fire. The enclosure is made of rigid aluminium alloy, or painted steel sheet. The F200 and F400 products are also available with auxiliary contacts. The products are EMC approved, when used with EMC cable glands. The handle is padlockable in On and Off position with max. 3 padlocks, and cover is interlocked. |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85363030 |
Country of Origin: | Bulgaria (BG) |
Popular Downloads | |
Data Sheet, Technical Information: | 1SCC340004B0201 |
VTT-S-5638-16 F200 | |
Instructions and Manuals: | 1SCC340166M0205 |
Mechanical Drawings: | OTFK1161313RM25.stp |
| |
Product Net Width: | 130 mm |
Product Net Height: | 165 mm |
Product Net Depth / Length: | 103 mm |
Product Net Weight: | 1.25 kg |
| |
Rated Operational Current AC-22A (Ie): | (380 ... 415 V) 20 A |
(690 V) 20 A | |
Rated Operational Current AC-23A (Ie): | (380 ... 415 V) 20 A |
(500 V) 20 A | |
(690 V) 12 A | |
Rated Operational Power AC-23A (Pe): | (380 ... 415 V) 11 kW |
(500 V) 11 kW | |
(690 V) 11 kW | |
Conventional Thermal Current (Ithe): | Fully Enclosed 32 A |
Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 750 V |
Rated Operational Voltage: | Main Circuit 750 V |
Rated Short-Circuit Making Capacity (Icm): | (690 V AC) 0.705 kA |
Rated Short-time Withstand Current (Icw): | for 1 s 0.5 kA |
Rated Conditional Short-Circuit Current (Inc): | 6.5 kA |
Power Loss: | at Rated Operating Conditions per Pole 0.6 W |
Pollution Degree: | 3 |
Handle Color: | Red |
Handle Type: | Round handle |
Position of Line Terminals: | Top In - Bottom Out |
Standards: | IEC 60947-1, -3 |
Number of Poles: | 3 |
Neutral Type: | No neutral terminal |
Connecting Capacity Main Circuit: | Screw Clamp 0.75 ... 10 mm² |
Screw Clamp / PE Terminal 3pc,1.5 ... 16 mm² | |
Cable Cross-Section: | 0.75 ... 10 mm² |
Cable Entry Position: | Up/Down |
Cable Outlets Per Side: | 2xM25+M20 / 2xM25+M20 |
Degree of Protection: | acc. to IEC 60529 IP65 |
Impact Resistance Rating: | Housing IK07 |
Enclosure Type: | Frontex1 |
Enclosure Material: | Aluminium |
Maximum Mounted Auxiliary Contacts: | 2 NO, 2 NC |
Mounted Auxiliary Contacts: | 1 NO, 0 NC |
Number of Auxiliary Contacts NC: | 0 |
Number of Auxiliary Contacts NO: | 1 |
Terminal Type: | Screw Terminals |
Tightening Torque: | acc. IEC 60947-1 0.8 N·m |
Mechanical Durability: | 20000 |
| |
Declaration of Conformity - CE: | 1SCC340064D2701 |
Instructions and Manuals: | 1SCC340166M0205 |
RoHS Information: | 1SCC340064D2701 |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 136 mm |
Package Level 1 Depth / Length: | 175 mm |
Package Level 1 Height: | 140 mm |
Package Level 1 Gross Weight: | 1.25 kg |
Package Level 1 EAN: | 6417019807607 |
| |
Object Classification Code: | Q |
ETIM 5: | EC000216 - Switch disconnector |
ETIM 6: | EC000216 - Switch disconnector |
ETIM 7: | EC000216 - Switch disconnector |
ETIM 8: | EC000216 - Switch disconnector |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |