Article: XT2H 160 TMA 125-1250 3p F F

Article: XT2H 160 TMA 125-1250 3p F F
XT2H 160 TMA 125-1250 3p F F
We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | XT2H 160 TMA 125-1250 3p F F |
Product ID: | 1SDA067603R1 |
EAN: | 8015644014995 |
Catalog Description: | XT2H 160 TMA 125-1250 3p F F |
Long Description: | C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 125 I3=625...1250 A |
| |
E-Number (Finland): | 3602495 |
EAN: | 8015644014995 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
| |
Product Net Width: | 90 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 82.5 mm |
Product Net Weight: | 1.567 kg |
| |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 130 mm |
Package Level 1 Height: | 208 mm |
Package Level 1 Depth / Length: | 145 mm |
Package Level 1 Gross Weight: | 1.649 kg |
Package Level 1 EAN: | 8015644014995 |
| |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| |
Circuit Breaker Type to be Associated: | Power Distribution |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour |
8000 cycle | |
Mechanical Durability: | Nr. Operations 240 cycles per hour |
Nr. Operations 25000 cycle | |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms |
CB with UVR 15 ms | |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 11.4 W |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | CB |
Rated Current (In): | 125 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Voltage (Ur): | 690 V |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 625…1250 A |
Rated Insulation Voltage (Ui): | 1000 V |
Rated Operational Voltage: | 690 V AC |
500 V DC | |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 100 kA |
(230 V AC) 100 kA | |
(240 V AC) 100 kA | |
(380 V AC) 70 kA | |
(415 V AC) 70 kA | |
(440 V AC) 65 kA | |
(500 V AC) 50 kA | |
(525 V AC) 30 kA | |
(690 V AC) 15 kA | |
(250 V DC) 2 Poles in Series 70 kA | |
(500 V DC) 3 Poles in Series 70 kA | |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 100 kA |
(230 V AC) 100 kA | |
(240 V AC) 100 kA | |
(380 V AC) 70 kA | |
(415 V AC) 70 kA | |
(440 V AC) 65 kA | |
(500 V AC) 50 kA | |
(525 V AC) 30 kA | |
(690 V AC) 15 kA | |
(250 V DC) 2 Poles in Series 70 kA | |
(500 V DC) 3 Poles in Series 70 kA | |
Rated Uninterrupted Current (Iu): | 160 A |
Release: | TMA |
Release Type: | TM |
Setting Range: | 87.5...125 A |
Short-Circuit Performance Level: | H |
Standards: | IEC |
Sub-type: | XT2 |
Terminal Connection Type: | Fixed Circuit-Breakers |
Version: | F |
| |
Data Sheet, Technical Information: | 1SDC210100D0206 |
1SDC210099D0206 | |
Declaration of Conformity - CE: | 9AKK106713A5901 |
Environmental Information: | 1SDL000190R0004 |
GL Certificate: | 1SDL000163R0093 |
Instructions and Manuals: | 1SDH000721R0001 |
LR Certificate: | 1SDL000163R0100 |
REACH Declaration: | LB-DT 18-21D |
RoHS Information: | LB-DT 17-21D |
| |
ETIM 4: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 6: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 7: | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
UNSPSC: | 39120000 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |