Article: XT4V 160 MA 20 Im=100...200 3p F F

Article: XT4V 160 MA 20 Im=100...200 3p F F

XT4V 160 MA 20 Im=100...200 3p F F
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration






























General Information
Extended Product Type: XT4V 160 MA 20 Im=100...200 3p F F
Product ID: 1SDA107704R1
EAN: 8056221028486
Catalog Description: XT4V 160 MA 20 Im=100...200 3p F F
Long Description: C.BREAKER TMAX XT4V 160 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MA Iu 10 A I3=100...200 A

Ordering
EAN: 8056221028486
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090

Dimensions
Product Net Width: 105 mm
Product Net Height: 160 mm
Product Net Depth / Length: 82.5 mm
Product Net Weight: 2.05 kg

Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 145 mm
Package Level 1 Height: 210 mm
Package Level 1 Depth / Length: 168 mm
Package Level 1 Gross Weight: 2.5 kg
Package Level 1 EAN: 8056221028486

Environmental
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Additional Information
Circuit Breaker Type to be Associated: Motor Protection
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
10000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 3
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 2.6 W
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: CB
Rated Current (In): 20 A
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 100…2000 A
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 200 kA
(230 V AC) 200 kA
(240 V AC) 200 kA
(380 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 150 kA
(500 V AC) 85 kA
(525 V AC) 70 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 100 kA
(500 V DC) 2 Poles in Series 100 kA
(500 V DC) 3 Poles in Series 100 kA
(750 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 200 kA
(230 V AC) 200 kA
(240 V AC) 200 kA
(380 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 150 kA
(500 V AC) 85 kA
(525 V AC) 70 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 100 kA
(500 V DC) 2 Poles in Series 100 kA
(500 V DC) 3 Poles in Series 100 kA
(750 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu): 160 A
Release: MA
Release Type: M
Short-Circuit Performance Level: V
Standards: IEC 60947
Sub-type: XT4
Terminal Connection Type: Fixed Circuit-Breakers
Version: F

Certificates and Declarations (Document Number)
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity - CE: 9AKK106713A5529
Environmental Information: 1SDL000190R0004
Instructions and Manuals: 1SDH000722R0001
1SDH000721R0505
REACH Declaration: LB-DT 18-21D
RoHS Information: LB-DT 17-21D

Classifications
ETIM 6: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 7: EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)