Article: XT7L 1250 Ekip Touch Meas.LSI 1250 3p FF

Article: XT7L 1250 Ekip Touch Meas.LSI 1250 3p FF
XT7L 1250 Ekip Touch Meas.LSI 1250 3p FF
We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | XT7L 1250 Ekip Touch Meas.LSI 1250 3p FF |
Product ID: | 1SDA100976R1 |
EAN: | 8056221010306 |
Catalog Description: | XT7L 1250 Ekip Touch Meas.LSI 1250 3p FF |
Long Description: | C.BREAKER TMAX XT7L 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC EKIP TOUCH MEASURING LSI R 1250 |
| |
EAN: | 8056221010306 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
| |
Product Net Width: | 210 mm |
Product Net Height: | 268 mm |
Product Net Depth / Length: | 166 mm |
Product Net Weight: | 9.7 kg |
| |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 280 mm |
Package Level 1 Height: | 350 mm |
Package Level 1 Depth / Length: | 360 mm |
Package Level 1 Gross Weight: | 11.2 kg |
Package Level 1 EAN: | 8056221010306 |
| |
Ambient Air Temperature: | Operation -40 ... 125 °C |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| |
Circuit Breaker Type to be Associated: | Power Distribution |
Current Type: | AC |
Electrical Durability: | 120 cycles per hour |
3000 cycle | |
Mechanical Durability: | 240 cycles per hour |
10000 cycle | |
Number of Poles: | 3 |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 57 W |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | CB |
Rated Current (In): | 1250 A |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Insulation Voltage (Ui): | 1000 V |
Rated Operational Voltage: | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 200 kA |
(230 V AC) 200 kA | |
(240 V AC) 200 kA | |
(380 V AC) 120 kA | |
(415 V AC) 120 kA | |
(440 V AC) 100 kA | |
(500 V AC) 85 kA | |
(525 V AC) 65 kA | |
(690 V AC) 50 kA | |
Rated Short-time Withstand Current (Icw): | 20 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 200 kA |
(230 V AC) 200 kA | |
(240 V AC) 200 kA | |
(380 V AC) 120 kA | |
(415 V AC) 120 kA | |
(440 V AC) 100 kA | |
(500 V AC) 85 kA | |
(525 V AC) 65 kA | |
(690 V AC) 50 kA | |
Rated Uninterrupted Current (Iu): | 1250 A |
Release: | Ekip Touch Measuring LSI |
Release Type: | EL |
Short-Circuit Performance Level: | L |
Standards: | IEC 60947 |
Sub-type: | XT7 |
Terminal Connection Type: | Fixed Circuit-Breakers |
Version: | F |
| |
Data Sheet, Technical Information: | 1SDC210100D0206 |
1SDC210099D0206 | |
Declaration of Conformity - CE: | 9AKK107046A9648 |
Environmental Information: | 1SDL000190R0004 |
Instructions and Manuals: | 1SDH002013A1001 |
1SDH002013A1002 | |
1SDH001821A1001 | |
REACH Declaration: | LB-DT 18-21D |
RoHS Information: | LB-DT 17-21D |
| |
ETIM 6: | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 7: | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |