Article: F204 B-40/0.3

Article: F204 B-40/0.3

F204 B-40/0.3 Residual Current Circuit Breaker
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration





General Information
Extended Product Type: F204 B-40/0.3
Product ID: 2CSF204592R3400
EAN: 8012542358138
Catalog Description: F204 B-40/0.3 Residual Current Circuit Breaker
Long Description: The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications. This product is particularly suitable for the protection against smooth d.c. earth fault currents.

Technical
Standards: IEC/EN 61008
Product Name: Residual Current Circuit Breaker
Type of Residual Current: B type
Rated Voltage (Ur): 230/400 V
Rated Operational Voltage: 230/400 V
Rated Insulation Voltage (Ui): 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
Input Voltage Type: AC
Rated Current (In): 40 A
Rated Residual Current: 300 mA
Rated Conditional Short-Circuit Current (Inc): 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics): 1 kA
Maximum Surge Current: 3 kA
Leakage Current Type: B
Rated Frequency (f): 50 / 60 Hz
Power Loss: at Rated Operating Conditions per Pole 1.81 W
Power Supply Connection: Arbitrary
Electrical Endurance: 10000 cycle
Number of Poles: 4
Operating Characteristic: Instantaneous
Position of Neutral Terminals: Right
Actuator Type: Toggle - Insulation group I - II, RAL 5015
Housing Type: Insulation group I - II, RAL 7035
Mounting Type: DIN rail
Options Provided: None
Accessories Available: Yes
Connecting Capacity: Busbar 10 mm²
Rigid 25 ... 25 mm²
Flexible 25 ... 25 mm²
Rated Cross-Section: 4 - Multi-Wired 0...25 mm²
1 - Solid-Core 25...25 mm²

Environmental
Ambient Temperature: -25...55 °C
Ambient Air Temperature: Operation -25...55 °C
Degree of Protection: IP2X
Pollution Degree: 2
RoHS Status: Following EU Directive 2011/65/EU
Environmental Information: Refer to RoHS
Technical UL/CSA
Short-Circuit Current Rating (SCCR): 0.3 A

Dimensions
Width in Number of Modular Spacings: 4
Product Net Width: 0.072 m
Product Net Height: 0.085 m
Product Net Depth / Length: 0.069 m
Product Net Weight: 0.380 kg
Built-In Depth (t2): 69 mm

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 80 mm
Package Level 1 Height: 41 mm
Package Level 1 Depth / Length: 94 mm
Package Level 1 Gross Weight: 0.415 kg
Package Level 1 EAN: 8012542358138
Package Level 2 Units: crate 3 piece
Package Level 2 Width: 246 mm
Package Level 2 Height: 94 mm
Package Level 2 Depth / Length: 80 mm

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85363030
E-Number (Finland): 3210599
E-Number (Sweden): 2160021
Replacement Product ID (NEW): 2CSF204568R3400
Country of Origin: Italy (IT)
Selling Unit of Measure: piece

Certificates and Declarations (Document Number)
CCC Certificate: 9AKK107492A0002
Declaration of Conformity - CE: 9AKK106713A5610
Environmental Information: Refer to RoHS
Instructions and Manuals: 9AKK106354A0846
RoHS Information: 2CSC423001K2702
Popular Downloads
Data Sheet, Technical Information: 9AKK107991A8329
Instructions and Manuals: 9AKK106354A0846

Classifications
ETIM 6: EC000003 - Residual current circuit breaker (RCCB)
ETIM 7: EC000003 - Residual current circuit breaker (RCCB)
ETIM 8: EC000003 - Residual current circuit breaker (RCCB)
EPLAN Catalog Tree: Electrical engineering / Protection devices / Ground fault current circuit breaker
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B: Business To Consumer
CN8: 85363030
Object Classification Code: F