Article: E880+254C100

We find the right product
for you
Official reseller
Expert engineering support
Configuration
):
General Information | |
Extended Product Type: | E880+254C100 |
Product ID: | 2CCG000263R0001 |
EAN: | 5413656647959 |
Catalog Description: | E880+254C100 High Performance MCB |
Long Description: | E880+251C100 High Performance MCB, 25 kA, 4 Pole, C characteristic, 100 A |
| |
Standards: | IEC/EN 60947-2 |
IEC/EN 60898-1 | |
Product Name: | High Performance MCB |
Tripping Characteristic: | C |
Rated Voltage (Ur): | 254/440 V AC |
500 V DC | |
Rated Operational Voltage: | 254/440 V AC |
500 V DC | |
Operational Voltage: | Maximum 230/400 V AC |
Minimum 12 V AC | |
Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 500 V AC |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Current (In): | 100 A |
Rated Operational Current (Ie): | 100 A |
Rated Short-Circuit Capacity (Icn): | (230 / 400 V AC) 15 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (240 / 415 V AC) 25 kA |
(254 / 440 V AC) 15 kA | |
(500 V DC) 10 kA | |
Rated Service Short-Circuit Breaking Capacity (Ics): | (240 / 415 V AC) 18 kA |
(254 / 440 V AC) 10 kA | |
(500 V DC) 10 kA | |
Frequency (f): | 50 / 60 Hz |
Rated Frequency (f): | 50 ... 60 Hz |
Power Loss: | 32 W |
at Rated Operating Conditions per Pole 8 W | |
Contact Position Indication: | ON / OFF / TRIP |
Energy Limiting Class: | 3 |
Mechanical Endurance (N | |
endu | 4000 cycle |
Number of Poles: | 4 |
Overvoltage Category: | IV |
Tightening Torque: | 3.5 N·m |
Actuator Marking: | I / O |
Housing Material: | Insulation group I, RAL 7035 |
Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
Mounting Position: | any |
Recommended Screw Driver: | Pozidriv 2 |
Remarks: | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captIIIe screw |
Number of Batteries: | 0 |
Connecting Capacity: | Flexible 1 ... 50 mm² |
Stranded 1 ... 70 mm² | |
Terminal Type: | Screw Terminals |
| |
Reference Ambient Air Temperature: | acc. to IEC60947-2 30 °C |
acc. to EN60898-1 30 °C | |
Degree of Protection: | IP20 |
Pollution Degree: | 3 |
Environmental Conditions: | Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle |
55°C @ 90-96% | |
25°C @ 90-100% | |
Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C | |
2 hour @ 70 °C | |
Resistance to Vibrations acc. to IEC 60068-2-6: | 2 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
Resistance to Shock acc. to IEC 60068-2-27: | 5 g |
30 ms | |
| |
Product Net Width: | 106 mm |
Product Net Height: | 95 mm |
Product Net Depth / Length: | 82.5 mm |
Product Net Weight: | 980 g |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 105 mm |
Package Level 1 Height: | 99 mm |
Package Level 1 Depth / Length: | 111 mm |
Package Level 1 Gross Weight: | 1010 g |
Package Level 1 EAN: | 5413656647959 |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Country of Origin: | Switzerland (CH) |
Selling Unit of Measure: | piece |
| |
Declaration of Conformity - CE: | No declaration needed |
Instructions and Manuals: | No document needed |
Popular Downloads | |
Data Sheet, Technical Information: | No document needed |
Instructions and Manuals: | No document needed |
| |
ETIM 6: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 7: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 8: | EC000042 - Miniature circuit breaker (MCB) |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B: | Business To Business |
CN8: | 85362020 |
Object Classification Code: | F |