Article: E880+252C125

We find the right product
for you
Official reseller
Expert engineering support
Configuration
):
General Information | |
| Extended Product Type: | E880+252C125 |
| Product ID: | 2CCG000318R0001 |
| EAN: | 5413656648000 |
| Catalog Description: | E880+252C125 High Performance MCB |
| Long Description: | E880+251C100 High Performance MCB, 25 kA, 2 Pole, C characteristic, 125 A |
| |
| Standards: | IEC/EN 60947-2 |
| IEC/EN 60898-1 | |
| Product Name: | High Performance MCB |
| Tripping Characteristic: | C |
| Rated Voltage (Ur): | 254/440 V AC |
| 250 V DC | |
| Rated Operational Voltage: | 254/440 V AC |
| 250 V DC | |
| Operational Voltage: | Maximum 230/400 V AC |
| Minimum 12 V AC | |
| Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 500 V AC |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Current (In): | 125 A |
| Rated Operational Current (Ie): | 125 A |
| Rated Short-Circuit Capacity (Icn): | (230 / 400 V AC) 15 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (240 / 415 V AC) 25 kA |
| (254 / 440 V AC) 15 kA | |
| (250 V DC) 10 kA | |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (240 / 415 V AC) 18 kA |
| (254 / 440 V AC) 10 kA | |
| (250 V DC) 10 kA | |
| Frequency (f): | 50 / 60 Hz |
| Rated Frequency (f): | 50 ... 60 Hz |
| Power Loss: | 18.8 W |
| at Rated Operating Conditions per Pole 9.4 W | |
| Contact Position Indication: | ON / OFF / TRIP |
| Energy Limiting Class: | 3 |
| Mechanical Endurance (N | |
| endu | 6000 cycle |
| Number of Poles: | 2 |
| Overvoltage Category: | IV |
| Tightening Torque: | 3.5 N·m |
| Actuator Marking: | I / O |
| Housing Material: | Insulation group I, RAL 7035 |
| Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position: | any |
| Recommended Screw Driver: | Pozidriv 2 |
| Remarks: | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captIIIe screw |
| Number of Batteries: | 0 |
| Connecting Capacity: | Flexible 1 ... 50 mm² |
| Stranded 1 ... 70 mm² | |
| Terminal Type: | Screw Terminals |
| |
| Reference Ambient Air Temperature: | acc. to IEC60947-2 30 °C |
| acc. to EN60898-1 30 °C | |
| Degree of Protection: | IP20 |
| Pollution Degree: | 3 |
| Environmental Conditions: | Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle |
| 55°C @ 90-96% | |
| 25°C @ 90-100% | |
| Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C | |
| 2 hour @ 70 °C | |
| Resistance to Vibrations acc. to IEC 60068-2-6: | 2 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
| Resistance to Shock acc. to IEC 60068-2-27: | 5 g |
| 30 ms | |
| |
| Product Net Width: | 54 mm |
| Product Net Height: | 95 mm |
| Product Net Depth / Length: | 82.5 mm |
| Product Net Weight: | 490 g |
| |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 105 mm |
| Package Level 1 Height: | 99 mm |
| Package Level 1 Depth / Length: | 60 mm |
| Package Level 1 Gross Weight: | 510 g |
| Package Level 1 EAN: | 5413656648000 |
| |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Country of Origin: | Switzerland (CH) |
| Selling Unit of Measure: | piece |
| |
| Declaration of Conformity - CE: | No declaration needed |
| Instructions and Manuals: | No document needed |
| Popular Downloads | |
| Data Sheet, Technical Information: | No document needed |
| Instructions and Manuals: | No document needed |
| |
| ETIM 6: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 7: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 8: | EC000042 - Miniature circuit breaker (MCB) |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Business |
| CN8: | 85362020 |
| Object Classification Code: | F |