Article: CM-TCN.011P

Article: CM-TCN.011P
CM-TCN.011P Temp. monitoring relays LCD+NFC, -200..+850°C, 24VAC/DC
We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | CM-TCN.011P |
Product ID: | 1SVR760740R0110 |
EAN: | 4013614552625 |
Catalog Description: | CM-TCN.011P Temp. monitoring relays LCD+NFC, -200..+850°C, 24VAC/DC |
Long Description: | Temperature monitoring relay CM-TCN.011P, Temp.-range -200..+850°C, width 45mm, digital adjustable, 3 threshholds, over temperature-, under temperature-, window monitoring, A1-A2=24V AC / DC, 3 c/o, Push-in connection terminals |
| |
EAN: | 4013614552625 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85364900 |
Popular Downloads | |
Data Sheet, Technical Information: | 2CDC112286C0201 |
Instructions and Manuals: | 1SVC750040M0001 |
| |
Product Net Width: | 45 mm |
Product Net Depth / Length: | 103.7 mm |
Product Net Height: | 85.6 mm |
Product Net Weight: | 0.265 kg |
| |
Function: | Overtemperature monitoring |
Undertemperature monitoring | |
Over- and undertemperature monitoring | |
Measuring Range: | -200 ... +850 °C |
Sensor Type: | PT100; PT1000; PTC; NTC; bimetal switch |
Rated Control Supply Voltage (Us): | 24 V AC/DC |
Rated Frequency (f): | Supply Circuit 50 Hz |
Supply Circuit 60 Hz | |
Supply Circuit DC Hz | |
Output: | 3 x 1 c/o contacts, configurable |
Terminal Type: | Screwless Terminals |
Rated Operational Current AC-12 (Ie): | (230 V) 4 A |
Rated Operational Current AC-15 (Ie): | (230 V) 3 A |
Rated Operational Current DC-12 (Ie): | (24 V) 4 A |
Rated Operational Current DC-13 (Ie): | (24 V) 2 A |
Minimum Switching Capacity: | 12 V |
100 mA | |
Rated Impulse Withstand Voltage (Uimp): | Measuring Circuit / Output Circuit 6 kV |
Output Circuit 1 / Output Circuit 2 4 kV | |
Supply Circuit / Measuring Circuit 6 kV | |
Supply Circuit / Output Circuit 6 kV | |
Rated Insulation Voltage (Ui): | Measuring Circuit / Output Circuit 600 V |
Output Circuit 1 / Output Circuit 2 300 V | |
Supply Circuit / Measuring Circuit 600 V | |
Supply Circuit / Output Circuit 600 V | |
Degree of Protection: | Housing IP50 |
Terminals IP20 | |
Overvoltage Category: | III |
Pollution Degree: | 2 |
Short-Circuit Protective Devices: | Output Circuit NC - F Type Fuses 6 A |
Output Circuit NO - F Type Fuses 10 A | |
Electrical Durability: | AC-12 100000 cycle |
Mechanical Durability: | 30000000 cycle |
Connecting Capacity: | Flexible with Ferrule 2x 0.5 ... 1.5 mm² |
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² | |
Flexible 2x 0.5 ... 1.5 mm² | |
Rigid 2x 0.5 ... 1.5 mm² | |
Wire Stripping Length: | 8 mm |
Mounting Position: | Any |
Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA: | Output Circuit 300 V AC |
Contact Rating UL/CSA: | B300 |
Connecting Capacity UL/CSA: | Flexible 2x 18-16 AWG |
Rigid 2x 20-16 AWG | |
| |
Ambient Air Temperature: | Operation -25 ... +60 °C |
Storage -40 ... +85 °C | |
RoHS Status: | Following EU Directive 2011/65/EU |
| |
CCC Certificate: | CCC_2018010303056014 |
CQC Certificate: | CQC2018010303056014 |
cULus Certificate: | cULus80947_E140448-20200622 |
Data Sheet, Technical Information: | 2CDC112286C0201 |
Declaration of Conformity - CCC: | 2020980303000208 |
Declaration of Conformity - CE: | 1SVD981067 |
Instructions and Manuals: | 1SVC750040M0001 |
RoHS Information: | 1SVD981067-0001 |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 97 mm |
Package Level 1 Height: | 109 mm |
Package Level 1 Depth / Length: | 52.5 mm |
Package Level 1 Gross Weight: | 0.293 kg |
Package Level 1 EAN: | 4013614552625 |
| |
Object Classification Code: | B |
ETIM 5: | EC001446 - Temperature monitoring relay |
ETIM 6: | EC001446 - Temperature monitoring relay |
ETIM 7: | EC001446 - Temperature monitoring relay |
eClass: | V11.0 : 27371810 |