Article: S3H 160 R 50 I 500 3p F F

Article: S3H 160 R 50 I 500 3p F F

S3H 160 R 50 I 500 3p F F
We find the right product for you
info@quadindustry.com
+49 (2191) 5992017
Official reseller
Expert engineering support

Configuration







General Information
Extended Product Type: S3H 160 R 50 I 500 3p F F
Product ID: 1SDA013397R1
ABB Type Designation: S3H 160 R50 FF 3P
EAN: 8015644133979
Catalog Description: S3H 160 R 50 I 500 3p F F
Long Description: CIRCUIT-BREAKER ISOMAX S3H 160 THREE-POLE FIXED WITH FRONT TERMINALS AND PROTECTIVE RELEASES THERMOMAGNETIC IN AC R 50-500 A

Ordering
EAN: 8015644133979
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090

Dimensions
Product Net Width: 178 mm
Product Net Height: 233 mm
Product Net Length: 200 mm
Product Net Depth / Length: 0.1035 m
Product Net Weight: 2.6 kg

Container Information
Package Level 1 Units: 1 piece
Package Level 1 Height: 233 mm
Package Level 1 Depth / Length: 178 mm
Package Level 1 Gross Weight: 5.6 kg
Package Level 1 EAN: 8015644133979

Additional Information
Electrical Durability: 10000
Number of Poles: 3
Order Multiple: 1.000 piece
Power Loss: 16.4 W
Product Main Type: SACE Isomax
Product Name: Moulded Case Circuit Breaker
Rated Current (In): 160 A
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Operational Voltage: 690 V AC
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (230 V AC) 100 kA
(220 V AC) 100 kA
(440 V AC) 50 kA
(500 V AC) 40 kA
(380 V AC) 65 kA
(690 V AC) 18 kA
Rated Uninterrupted Current (Iu): 160.0 A
Release Type: TadjM10
Short-Circuit Performance Level: H
Standards: IEC-947-2(D)
Sub-type: S3
Suitable For: Isomax S3
Suitable for Product Class: Isomax
Terminal Connection Type: Front
Test Voltage at Industrial Frequency for 1 Minute: 3000 V
Version: Fixed

Certificates and Declarations (Document Number)
Data Sheet, Technical Information: ITSCE-604050012
Declaration of Conformity - CE: 1SDL000286R001
Instructions and Manuals: ITSCE-601780022
ITSCE-605071013

Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000