Article: S701-E100+H2WR

Article: S701-E100+H2WR
S701-E100+H2WR Selective Main Circuit Breaker
We find the right product
for you
Official reseller
Expert engineering support
Configuration
):
General Information | |
| Extended Product Type: | S701-E100+H2WR |
| Product ID: | GHS7010316R0639 |
| EAN: | 4016779457507 |
| Catalog Description: | S701-E100+H2WR Selective Main Circuit Breaker |
| Long Description: | S701-E100+H2WR sel. main CB + AUX E-Char.,25kA,100A,1P,2xCO |
| |
| Standards: | DIN EN 60947-2 |
| E DIN VDE 0645:2003-09 | |
| Product Name: | Selective Main Circuit Breaker |
| Tripping Characteristic: | E (Selective) |
| Suitable for Isolation: | Yes |
| Rated Voltage (Ur): | 230 V AC |
| Rated Operational Voltage: | 230 / 400 V AC |
| Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 690 V |
| Rated Impulse Withstand Voltage (Uimp): | 6 kV |
| Dielectric Test Voltage: | 50/60 Hz, 1 min: 2 kV |
| Rated Current (In): | 100 A |
| Rated Operational Current (Ie): | 100 A |
| Rated Short-Circuit Capacity (Icn): | (230 / 400 V AC) 25 kA |
| Rated Frequency (f): | 50 / 60 Hz |
| Power Loss: | at Rated Operating Conditions per Pole 14.4 W |
| Power Supply Connection: | Arbitrary |
| Contact Position Indication: | Red ON / Green OFF |
| Mechanical Endurance (N | |
| endu | 1000 cycle |
| Number of Poles: | 1 |
| Number of Auxiliary Contacts CO (SPDT): | 2 |
| Overvoltage Category: | IV |
| Product Range: | S700 |
| Tightening Torque: | 3 ... 3.5 N·m |
| Actuator Marking: | I / O |
| Options Provided: | with auxiliary attached |
| Mounting on DIN Rail: | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position: | Any |
| Recommended Screw Driver: | Cross Recess Pozidriv 2 |
| Slotted 1 x 5.5 | |
| Accessories Available: | Yes |
| Connecting Capacity: | Flexible with Ferrule 2.5 ... 50 mm² |
| Flexible 2.5 ... 70 mm² | |
| Rigid 2.5 ... 50 mm² | |
| Stranded 2.5 ... 50 mm² | |
| Installation Size: | acc. to DIN 43880 6 |
| |
| Ambient Air Temperature: | Operation -25 ... +55 °C |
| Storage -40 ... +70 °C | |
| Ambient Air Temperature Compensation: | Yes |
| Degree of Protection: | IP20 |
| Pollution Degree: | 3 |
| Environmental Conditions: | 28 cycles |
| with 55 °C / 90-96 % | |
| and 25 °C / 95-100 % | |
| Resistance to Vibrations acc. to IEC 60068-2-6: | 2g, 20 cycles at 5 ... 150 ... 5Hz |
| Resistance to Shock acc. to IEC 60068-2-27: | 30g / 3 shocks / 11 ms |
| RoHS Status: | Following EU Directive 2011/65/EU |
| Environmental Information: | 1SAA93002 |
| |
| Product Net Width: | 44 mm |
| Product Net Height: | 145 mm |
| Product Net Depth / Length: | 91 mm |
| Product Net Weight: | 0.56 kg |
| |
| Package Level 1 Units: | 3 piece |
| Package Level 1 Width: | 150 mm |
| Package Level 1 Height: | 105 mm |
| Package Level 1 Depth / Length: | 165 mm |
| Package Level 1 Gross Weight: | 1.8 kg |
| |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Country of Origin: | Czech Republic (CZ) |
| Selling Unit of Measure: | piece |
| |
| Declaration of Conformity - CE: | 2CDK415029D2702 |
| Environmental Information: | 1SAA93002 |
| Instructions and Manuals: | 2CDC415008D0101 |
| RoHS Information: | 2CDK400009K0201 |
| Popular Downloads | |
| Data Sheet, Technical Information: | 2CDC415008D0101 |
| Instructions and Manuals: | 2CDC415008D0101 |
| |
| ETIM 6: | EC001047 - Selective main line circuit breaker |
| ETIM 7: | EC001047 - Selective main line circuit breaker |
| ETIM 8: | EC001047 - Selective main line circuit breaker |
| EPLAN Catalog Tree: | Electrical engineering / Protection devices / Safety switch |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Consumer |
| CN8: | 8536 20 90 |
| UNSPSC: | 39121614 |
| eClass: | V11.0 : 27141903 |
| Object Classification Code: | F |