Article: T900DU-650

We find the right product
for you
Official reseller
Expert engineering support
Configuration
General Information | |
Extended Product Type: | T900DU-650 |
Product ID: | GJZ6021001R0003 |
EAN: | 4013614076039 |
Catalog Description: | T900DU-650 Thermal Overload Relay |
Long Description: | T900DU-650 Thermal Overload Relay Trip class 10A, 465-650A |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85364900 |
Popular Downloads | |
Data Sheet, Technical Information: | 1SBC100173C0201 |
Data Sheet, Technical Information (Part 2): | GJZ6000501F0003 |
Instructions and Manuals: | GJZ5207002P0002 |
Dimension Diagram: | 1SAZ600401F0001 |
| |
Product Net Width: | 245 mm |
Product Net Height: | 96 mm |
Product Net Depth / Length: | 207 mm |
Product Net Weight: | 2.585 kg |
| |
Setting Range: | 465 ... 650 A |
Rated Operational Voltage: | Auxiliary Circuit 440 V DC |
Auxiliary Circuit 500 V AC | |
Main Circuit 1000 V AC | |
Rated Operational Current (Ie): | 650 A |
Rated Operational Current AC-3 (Ie): | 650 A |
Rated Frequency (f): | Auxiliary Circuit 50 Hz |
Auxiliary Circuit 60 Hz | |
Auxiliary Circuit DC | |
Main Circuit 50 Hz | |
Main Circuit 60 Hz | |
Rated Impulse Withstand Voltage (Uimp): | Auxiliary Circuit 6 kV |
Main Circuit 8 kV | |
Rated Insulation Voltage (Ui): | 1000 V |
Number of Poles: | 3 |
Number of Auxiliary Contacts NC: | 1 |
Number of Auxiliary Contacts NO: | 1 |
Number of Protected Poles: | 3 |
Conventional Free-air Thermal Current (Ith): | Auxiliary Circuit NC 10 A |
Auxiliary Circuit NO 6 A | |
Rated Operational Current AC-15 (Ie): | (120 V) NC 3 A |
(120 V) NO 1.5 A | |
(240 V) NC 3 A | |
(240 V) NO 1.5 A | |
(400 V) NC 1.9 A | |
(400 V) NO 1 A | |
(440 V) NC 1 A | |
(440 V) NO 1 A | |
(500 V) NC 1 A | |
(500 V) NO 1 A | |
Rated Operational Current DC-13 (Ie): | (125 V) NC 0.25 A |
(125 V) NO 0.25 A | |
(24 V) NC 1.25 A | |
(24 V) NO 1.25 A | |
(250 V) NC 0.12 A | |
(250 V) NO 0.04 A | |
(60 V) NC 0.25 A | |
(60 V) NO 0.25 A | |
Degree of Protection: | IP20 |
Pollution Degree: | 3 |
Connecting Capacity Main Circuit: | Bar < 22.0 x 41.5 mm² |
Recommended Screw Driver: | Main Circuit Pozidriv 2 |
Standards: | IEC/EN 60947-1 |
IEC/EN 60947-4-1 | |
IEC/EN 60947-5-1 | |
UL 60947-1 | |
UL 60947-4-1 | |
Technical UL/CSA | |
Ampere Rating UL/CSA: | 650 A |
Contact Rating UL/CSA: | (NC:) B600 |
(NO:) C300 | |
| |
Ambient Air Temperature: | Operation -25 ... +55 °C |
Operation Compensated -25 ... +55 °C | |
Storage -40 ... +70 °C | |
Ambient Air Temperature Compensation: | Yes |
Maximum Operating Altitude Permissible: | 2000 m |
Resistance to Shock acc. to IEC 60068-2-27: | 11 ms Pulse 12g |
RoHS Status: | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| |
BV Certificate: | 1SAA941000-0201 |
CB Certificate: | 1SAA941007-2001 |
cUL Certificate: | cUL_E48139 |
Declaration of Conformity - CE: | 1SAD938501-0002 |
GL Certificate: | 1SAA941006-0403 |
GOST Certificate: | 1SAA941000-2704 |
Instructions and Manuals: | GJZ5207002P0002 |
LR Certificate: | 1SAA941000-0503 |
RMRS Certificate: | 1SAA941000-0703 |
RoHS Information: | 1SAA941004-4402 |
UL Certificate: | UL_E48139 |
| |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 273 mm |
Package Level 1 Height: | 145 mm |
Package Level 1 Depth / Length: | 250 mm |
Package Level 1 Gross Weight: | 2.895 kg |
Package Level 1 EAN: | 4013614076039 |
| |
Object Classification Code: | F |
ETIM 4: | EC000106 - Thermal overload relay |
ETIM 5: | EC000106 - Thermal overload relay |
ETIM 6: | EC000106 - Thermal overload relay |
ETIM 7: | EC000106 - Thermal overload relay |
eClass: | V11.0 : 27371501 |
UNSPSC: | 39121520 |
IDEA Granular Category Code (IGCC): | 5364 >> Overload relay |