The small Starter Kit Safe Link is available fully assembled and wired in a practical case.
Technical data
Type | Starter Kits |
Model | Gateway with integrated Safety Monitor |
Protection rating IP20: IP40: Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. IP54:
Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP20 |
Fieldbus interface Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS AS-i gateway: interface for a PROFIBUS fieldbus PROFIBUS AS-i Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS AS-i IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus/TCP AS-i gateway: interface for an EtherNet/IP+ Modbus/TCP fieldbus BACnet/IP AS-i gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix AS-i gateway: interface for the Compact-/MicroLogix backplane POWERLINK AS-i gateway: interface for an POWERLINK fieldbus | PROFINET |
Number of AS-i networks, number of AS-i Master Standard devicesSingle Master: 1 AS-i network, 1 AS-i Master. 2 AS-i networks, 2 AS-i Masters. Safety devicesSingle Master: | 2 AS-i networks, 2 AS-i Masters |
1 power supply, 1 gateway for 2 AS-i networks, inexpensive power supplies yes, max. 4 A/AS-i network: Operation with short cable lengths with standard 24 V power supply possible.
Should one AS-i power supply fail, switching to the other AS-i power supply allows all the diagnostics functions to be maintained and the unaffected AS-i network continues to operate. 1 AS-i power supply per AS-i network. | yes, max. 4 A/AS-i network |
Diagnostic and configuration interface USB: Access to AS-i Master and Safety Monitor with Bihl+Wiedemann proprietary software by using the USB interface. Access to AS-i Master and Safety Monitor with Bihl+Wiedemann software by using the Ethernet diagnostic interface or Ethernet fieldbus interface. Access to AS-i Master and Safety Monitor with Bihl+Wiedemann software by using the Ethernet diagnostic interface. Access to AS-i Master and Safety Monitor with Bihl+Wiedemann software or via Modbus TCP by using the Ethernet diagnostic interface. For a full-fledged Modbus TCP fieldbus interface use one of our Modbus TCP gateways in stainless steel or Modbus TCP gateways with integrated safety monitor.
Access to AS-i Master and Safety Monitor with Bihl+Wiedemann software by using the Ethernet fieldbus interface or by using an adapter cable via RS 232 interface.
Access to AS-i Master and Safety Monitor with Bihl+Wiedemann software by using an adapter cable via RS 232 interface.
The latest version of the device description file of the gateway/gateway with integrated safety monitor (GSD, GSDML, EDS, etc.) is available in the Downloads section of the respective device. | Ethernet fieldbus + Ethernet diagnostic |
Recognition of duplicate AS-i addresses Detects whether the same address has been assigned to two AS-i slaves. Frequent error when using a handheld addressing device. | yes |
AS-i fault detector Checks the AS-i line for interference effects such as noise, external voltages, ... | yes |
Programming in C Using a C-program offers the possibility to run mini-PLC functions with a gateway. | optional |
Inputs digital, EDM An externally connected relay (contactor) can be connected via a feedback loop to the Safety Monitor for monitoring purposes. | 6 |
Inputs Safety, SIL 3, Cat. 4 | 3 x 2 channels |
Inputs safety, expandable to | max. 62 x 2 channels, max. 1922 in max. configuration |
Outputs Safety, SIL 3, cat. 4 | 6 release circuits, 6 x fast electronic safe outputs |
Safety outputs, independent according to SIL 3, expandable to | max. 32, max. 992 in max. configuration |
Safety communication | Safe Link |